Select model:
SWEP B16Hx100 Heat exchanger

Price without VAT: | £405.00435.00 € | ||||||||||||
Price with VAT: | 526.35 € | ||||||||||||
Delivery costs: | EU 23 € | ||||||||||||
Availability: |
| ||||||||||||
Typical use: | Developed especially for water/water applications: heating and hot water (smaller heating stations), solar collectors, as plate oil cooler (oil/water), etc. Capacity . | ||||||||||||
Recommended max. flow 1): | 13 m3/h | ||||||||||||
Brazing material: | copper | ||||||||||||
Model version: | plate exchanger from stainless steel (AISI 316) | ||||||||||||
Dimensions (H × W × D): | 376 × 119 × 234 mm | ||||||||||||
Related products: | Insulation EPP 16x100, Ref 16x100 | ||||||||||||
Testing pressure: | 50 bar | ||||||||||||
Weight: | 13.9 kg | ||||||||||||
Product sheet: | B16.pdf ![]() ![]() | ||||||||||||
Item No. 2): |
| ||||||||||||
Connections: |
| ||||||||||||
Notes: | Click to expand notes | ||||||||||||
1) | The maximum recommended flow is calculated for water to limit pressure losses to 30 kPa. Also the flow velocity at the inlet to the exchanger is kept under 5.5 m/s to prevent erosion from water. | ||||||||||||
2) | SC-Y intermediate pressure: for water/water use (approx. 20 bar) SC-S standard pressure: for water/water use, some refrigerants (approx. 30 bar) SC-M medium pressure: for refrigerants (approx. 48 bar) SC-F intermediate pressure: for refrigerants (approx. 50 bar) SC-H high pressure: for refrigerants (approx. 55 bar) SC-D, SC-E higher pressure: for CO2 (approx. 55 bar) SC-U ultra high pressure: for CO2 (approx. 100 bar) SC-S: plates AISI 316, copper brazing NC-S: plates AISI 304, copper brazing SN-S: plates AISI 316, nickel brazing SPS-S: plates AISI 316, AISI 316 brazing (All Steel) |